Re: 151 Front St Toronto (Torix) (cooling fixed)

  • From: Mike Tancsa
  • Date: Fri Aug 15 05:45:00 2003



The building air conditioning has been fixed as of 5min ago (5:35 eastern). The temp has already dropped 3 degrees C on my router intake ports. Still no word on why their building generators failed nor what actually took out the cooling system.

---Mike

At 02:30 AM 15/08/2003 -0400, Mike Tancsa wrote:

At 08:26 PM 14/08/2003 -0700, Eric Kuhnke wrote:

TORIX is off the net
traces to peer1 routers/hosts at 151 front die before reaching toronto
the rumor mill has it that 151 front's generator system failed utterly...

Just called my colo provider (GT/360) and they said the air conditioners are still not fully functional. The temp is still rising for my equipment, but its not rising nearly as fast as before.

Temperature readings:
chassis inlet measured at 38C/100F
chassis outlet 1 measured at 41C/105F
chassis outlet 2 measured at 46C/114F
chassis outlet 3 measured at 52C/125F :Temperature in Warning range!

---Mike